Certificates :

Application

Fixed wiring in control panels, switch boadrs and various electrical enclosures and also used as fixed installation
cables in various electromechanical and electronic equipments.

* Minimum recommended installation temperature -15°C
For core identification, diameter tolerances and other details see technical information section

CONDUCTOR : “Electrolytic, stranded, annealed bare copper wire IEC 60228
Class 5 (Class 2 and / or tinned on request)”
INSULATİON : “Halogen free, flame retardant, cross linked polyolefin
compound (HF90).”
COLOR : Black, red, blue and other colours

CONSTRUCTION : IEC 60092 / 353
TESTS AND MATERIAL : IEC 60092 / 350-360
FLAME RETARDANT : IEC 60332 / 1-2, IEC 60332 / 3-22 Cat A
HALOGEN CONTENT : IEC 60754 / 1-2
SMOKE EMISSION : IEC 61034 / 1-2 ( DIN EN 50268 / 1-2)
OZON RESISTANCE : IEC60811 / 403
TEMPERATURE RANGE : -40°C / + 90°C
MIN. BENDING RADIUS (FIXED) : 4 x D
RATED VOLTAGE : 0,6 / 1 kV
TEST VOLTAGE : 3,5 kV

Cross Section (mm2)Nominal Overall Diameter (mm)Approximate Weight (kg / km)Bending Radius Fixed Min. (mm)Max Resistance of Conductors at 20°C (ohm / km)Current Carrying Capacity at 45°C (A)
1 x 12.7151119.516
1 x 1,52.9191213.321
1 x 2,53.228137.9829
1 x 43.741154.9539
1 x 64.259173.350
1 x 105.598221.9171
1 x 166.2148251.2193
1 x 258.6240350.78122
1 x 359.7330390.554152
1 x 5011.6464470.386195
1 x 7013648530.272240
1 x 9514.9841600.206286
1 x 120171076680.161332
1 x 15018.81336760.129382
1 x 18521.51675860.106432
1 x 240242172960.0801508
1 x 30026.627031070.0641590